A NUMERICAL STUDY FOR COATING OF VENTILATION DUCTS USING JET INJECTION

Yükleniyor...
Küçük Resim

Tarih

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Vinca Inst Nuclear Sci

Erişim Hakkı

info:eu-repo/semantics/openAccess

Özet

In this study, the performance of a novel method where an antibacterial solution is pressurized and sprayed into recirculated air through nozzles, is investigated numerically. This resembles a jet in a cross-flow problem where the antibacterial solution mixes with ventilation air and further adheres to the inner surfaces of the duct. The motion of particles dispersed in antibacterial solution is described as the advection of a passive scalar, i.e., temperature, allowing for a single-phase flow solution. The effectiveness of the coating is evaluated by the temperature distribution on the inner surfaces of the duct. Single phase 3-D turbulent flow of air at two different temperatures is modeled and the velocity and temperature fields in the ventilation duct were calculated using the commercial code ANSYS FLUENT. The numerical model is validated by experiments conducted on a full-scale test rig, in terms of temperature. The numerical calculations were conducted in four series: where the effect of the nozzle arrangement, the jet injection angle, the jet-to-crossflow velocity ratio, and a time-dependent jet velocity profile of a sinusoidal wave form are investigated. The numerical solutions show that the coating is highly inefficient for velocity ratios less than 3.3, and the period of time-varying jet stream has little effect on the coating performance.

Açıklama

Anahtar Kelimeler

antibacterial coating, indoor air quality, jet in cross-flow, temperature measurement, computational fluid dynamics

Kaynak

Thermal Science

WoS Q Değeri

Scopus Q Değeri

Cilt

27

Sayı

5A

Künye

Onay

İnceleme

Ekleyen

Referans Veren